MKP 800

External dimensions (LxWxH): 2160x1900x2350 mm
Max. nominal power: do 630 kVA
Empty skeleton weight: 5600 kg
r1

COMPACT KIOSK-TYPE TRANSFORMER STATION GRÄPER MKP 800

HV nominal voltage: 3 AC 22 kV 50 Hz

LV nominal voltage: 3/PEN AC 420/242 V 50 Hz / TN-C,

Frequency: 50 Hz

Transformer nominal power: to 630 kVA

HV bus-bars nominal current: according to HV switchgear type to 630 A

LV bus-bars nominal current: to 1000 A

HV/LV distributor nominal insulation voltage: 24 kV / 1000 V

HV distributor short-time / dynamic current: 16 kA / 40 kA

LV distributor short-time / dynamic current: do 25 kA / do 60 kA

HV/LV distributor cover: IP 65 / IP 20

Whole station cover: IP 23D

Cover class: K 20

External dimensions (LxWxH): 2160x1900x2350 mm

Empty skeleton weight: cca 5600 kg

Environment:

  • 1.1. basic (inside the kiosk-type TS room),
  • 4.1.1. external, ordinary (outside the TS room)

Exposure class:

  • for internal components: XC1
  • for external components: XC4, XF1, XA1.

Operating conditions:

  • ambient temperature –40°C ≤ t ≤ + 40°C
  • altitude up to 1000 m asl

Note: If the transformer substation is used in different climate and operating conditions, the TS supplier must be consulted.