ePrivacy and GPDR Cookie Consent management by TermsFeed Privacy Policy and Consent Generator

GA VR 232/714

External dimensions (LxWxH): 7140x2320x3560
Max. nominal power: 2 x 1000 kVA
Empty skeleton weight: 29000 kg

INTERNALLY CONTROLLED COMPACT KIOSK-TYPE TRANSFORMER STATION GRÄPER GA VR 232/714

HV nominal voltage: 3 AC 22 kV (35 kV) 50 Hz

LV nominal voltage: 3/PEN AC 420/242 V 50 Hz / TN-C,

Frequency: 50 Hz

Transformer nominal power: to 2x1 000 kVA

HV bus-bars nominal current: regarding HV distributor´s type to 630 A

LV bus-bars nominal current: to 1 500 A

HV / LV distributor nominal insulation voltage: 24 kV / 1 000 V

HV distributor short-time / dynamic current: 16 kA / 40 kA

LV distributor short-time / dynamic current: do 30 kA / do 60 kA

LV distributor cover: IP 20

Whole station cover: IP 23D

Temperature coefficient (Cover class): K 20

Empty skeleton weight: cca 29 000 kg (in exposed aggregate concrete design)

External dimensions: 7 140x2 320x3 550 mm (without roof overlap)

Environment:

  • 3.1.1. basic (within the kiosk-type TS rooms),
  • 4.1.1. ambient, ordinary (outside the TS rooms -)

Exposure class:

  • for internal components: XC1
  • for external components: XC4, XF1, XA1.

Operating conditions:

  • ambient temperature –40°C ≤ t ≤ + 40°C
  • altitude up to 1 000 m asl.

Note: If the transformer substation is used in different climate and operating conditions, the TS supplier is must be consulted.

Precision. Innovation. Quality.

We are committed to achieving only perfect results.

Contact Form