MKP 1600

External dimensions (LxWxH): 2550x2500x2650 mm
Max. nominal power: 1600 kVA
Empty skeleton weight: 8000 kg

COMPACT KIOSK-TYPE TRANSFORMER STATION GRÄPER MKP 1600

HV nominal voltage: 3 AC 22 kV 50 Hz

LV nominal voltage: 3/PEN AC 420/242 V 50 Hz / TN-C,

Frequency: 50 Hz

Transformer nominal power: to 1600 kVA

HV bus-bars nominal current: according to HV switchgear type to 630 A, TS outlet field 200A

LV bus-bars nominal current: to 2500 A

HV/LV distributor nominal insulation voltage: 24 kV / 1000 V

HV distributor short-time / dynamic current: 16 kA / 40 kA

LV distributor short-time / dynamic current: to 30 kA / to 60 kA

HV/LV distributor cover: IP 65 / IP 20

Whole station cover: IP 23D

Cover class: K 20

External dimensions (LxWxH): 2550x2300x2650 mm

Empty skeleton weight: cca 7900 kg

Environment:

  • 3.1.1. basic (inside the kiosk-type TS room),
  • 4.1.1. outside, ordinary (outside the TS room )

Exposure class:

  • for internal components: XC1
  • for external components: XC4, XF1, XA1.

Operating conditions:

  • ambient temperature –40°C ≤ t ≤ + 40°C
  • altitude up to 1000 m asl.

Note: If the transformer substation is used in different climate and operating conditions, the TS supplier is must be consulted.